Resistance and Reactance per km of Copper and Aluminium cables

Custom Search
For the purpose of calculating voltage drop within a cable, the table below gives the reactance and resistance values for Copper and Aluminium cables:

Values for Copper Cables


Cable Size, S (mm2) Single - Core Cable Two - Core/Three Core Cables
R(Ω/km) @ 80°C X (Ω/km) @ 80°C R(Ω/km) @ 80°C X(Ω/km) @ 80°C
1.5 14.8 0.168 15.1 0.118
2.5 8.91 0.156 9.08 0.109
4 5.57 0.143 5.68 0.101
6 3.71 0.135 3.78 0.0955
10 2.24 0.119 2.27 0.0861
16 1.41 0.112 1.43 0.0817
25 0.889 0.106 0.907 0.0813
35 0.641 0.101 0.654 0.0783
50 0.473 0.101 0.483 0.0779
70 0.328 0.0965 0.334 0.0751
95 0.326 0.0975 0.241 0.0762
120 0.188 0.0939 0.191 0.074
150 0.153 0.0928 0.157 0.0745
185 0.123 0.0908 0.125 0.0742
240 0.0943 0.0902 0.0966 0.0752
300 0.0761 0.0895 0.078 0.075

Values for
Aluminium Cables


Cable Size, S (mm2) Single - Core Cable Two - Core/Three Core Cables
R(Ω/km) @ 80°C X (Ω/km) @ 80°C R(Ω/km) @ 80°C X(Ω/km) @ 80°C
1.5 24.384 0.168 24.878 0.118
2.5 14.680 0.156 14.960 0.109
4 9.177 0.143 9.358 0.101
6 6.112 0.135 6.228 0.0955
10 3.691 0.119 3.740 0.0861
16 2.323 0.112 2.356 0.0817
25 1.465 0.106 1.494 0.0813
35 1.056 0.101 1.077 0.0783
50 0.779 0.101 0.796 0.0779
70 0.540 0.0965 0.550 0.0751
95 0.389 0.0975 0.397 0.0762
120 0.310 0.0939 0.315 0.074
150 0.252 0.0928 0.259 0.0745
185 0.203 0.0908 0.206 0.0742
240 0.155 0.0902 0.159 0.0752
300 0.125 0.0895 0.129 0.075