How to change the Rotation Direction and Wire Configuration – Star or Delta - of Electric Motors

The direction of rotation of an electric motor can be changed anytime and easily at the motor terminals. In three-phase motors, the windings configuration can easily be changed from a star or Y connection to a delta or mesh connection at the motor terminal box.

Three-phase Electric Motors
The windings of AC motors can either be connected in star(Y)-connection or in delta(Δ)-connection.The standard that deals with this winding connection and designated marking of the terminal box is IEC 60034-8. According to this standard, the phases of motor windings are defined by W, U, V

Star or Y Connection
For a motor with terminal markings as W1, U1, V1 and W2, U2, V2 respectively, proceed as follows:
Short-circuit the terminals W2, U2 and V2 and connect the mains to the W1, U1 and V1 to get a star(Y)-connection. See diagram below:
 
Delta(Δ) Connection
When connecting the end of a phase to the start of another phase you get a delta(Δ)-connection. Connect W2 to U1, U2 to V2, V1 to W1 as shown below:

How to Change the Rotation of a Three-phase Electric Motor
The direction of rotation for the motor shaft of an AC motor is defined in IEC 60034-8 as either CW (clockwise) or CCW (counter-clockwise), when looking into the motor shaft. The direction of rotation of a three-phase AC motor can be changed at the terminal box. This is done by interchanging two of the line cables, e.g switch L1 and L2.
When dealing with a single-phase motor, YOU MUST ALWAYS CHECK the wiring diagram from the manufacturer's manual to get direction on how to change the direction of rotation of the motor.



You May Also Like: