How to Wire a Photocell Switch to Lighting Loads with a Contactor

Custom Search

We have already discussed how to install and wire a photocell switch in a lighting installation and how to size a photocell for a lighting installation. We noted that the photocell switch is an energy saving device used to help conserve energy during the day and switch on the lighting installation during night-time.

Photocell sensors or switches come in various voltage and current ratings. For lighting loads under 5 Amps, it may be possible to wire the photocell switch directly to the lighting load circuit.

However, with large lighting loads, the photocell sensor has to be used indirectly to switch on and off the lighting load using a contactor. For example, let us say you have twenty (24) pieces of 250W High Pressure Sodium Lamps providing lighting to a small sized industrial complex, evidently it is not possible to wire the photocell sensor directly to the lighting loads!

What will be required is a higher current rated 3-phase contactor to power the lights, while a photocell can be wired to energize the contactor coil. During the day, the lights will be switched off and during the night when the photocell activates as a result of increased resistance, the lights come on.

How do we then Wire a Photocell with a Contactor?
The schematic wiring diagram below shows how to wire a photocell switch with a 3-phase contactor to power nine (9), 250W lighting loads:

Note that on the photocell sensor, L1 is the live wire, N is the neutral wire and Lo, is the load wire which goes to energize the contactor coil which must be rated for the phase voltage (L1-N or L2-N or L3 -N). Common phase voltage levels are 120V, 208V or 240V.

As shown in the schematic above, power goes into the circuit breaker (used for overload as well as short circuit protection). From the circuit breaker, power goes through the power contactor. During the day time, the Photocell sensor switch is off and the lamps are off. During the night time, the photocell sensor comes on energizing the coil of the contactor thereby supplying light to the lighting loads.

 

How to Calculate 1-Phase and 3-phase Motor Full Load Current (FLC)

Custom Search

To calculate the full load current of a single phase or 3-phase AC motor is pretty straight forward. However, the terms input power and shaft power of the motor must be fully understood otherwise errors will be made in this supposed simple calculation.

The input power of an AC motor is the power it draws when it connected to a 1-phase or 3-phase voltage source. The motor then speeds up, develops a torque and outputs a shaft power.

The shaft power however is the mechanical power output from the motor after the motor losses in the stator, rotor, windings and other losses have been accounted for. The relationship between Input electrical power and shaft power which is mechanical is given by:

Output Shaft Power of a Motor in KW = Input Electrical Power in KW x Motor Efficiency

It is therefore possible to calculate the  input electrical power when we know the details about the motor’s power supply, i.e., voltage, power factor, absorbed current and efficiency.

However as is common with most electric motors, the power rating in either KW or HP is usually the shaft power the motor can deliver to a load. This shaft power is dependent on the line voltage, power factor, full load current and the motor efficiency as illustrated below:

In Europe, shaft power is usually measured in kilowatts (KW). In the USA, however, shaft power is measured in terms of horsepower (HP).

Shaft Power delivered by a single-phase motor is given by:

Where:

U = Line voltage

I = Line current or Full Load Current

CosØ = Power Factor

ɳ = Motor efficiency


Shaft Power delivered by a 3-phase motor is given by:

3-phase Motor Shaft Power in kW   =

U * I *CosØ*√3*ɳ/1000


Where:

U = Line voltage

I = Line current or Full Load Current

CosØ = Power Factor

ɳ = Motor efficiency


How to calculate 1-phase & 3-phase Motor Load current 
To calculate Motor Load current applying the above formulas, here we present some sample calculations:
Suppose we have a 1.5HP, 1-phase AC motor powered by 240V source with a design power factor of 0.8 and efficiency of 85%, the full load current will be arrived at by manipulating the power formula for 1-phase motors to give the motor full load current as :

Full Load Current, I   =

Single Power in KW *1000/(U* CosØ* ɳ)

Here:

U = 240

CosØ = 0.8

ɳ = 0.85

Power in KW = 1.5 *746/1000 = 1.119

Note 1 HP = 746W

Therefore, I =

(1.119 * 1000)/(240 * 0.8*0.85) = 6.86 Amps


Suppose we have a 3-phase, 10KW, AC Motor with 415V, line voltage 3-phase power source and power factor 0.8 and efficiency of 88%, the full load current will be arrived at by manipulating the power formula for 3-phase motors to give the motor full load current as:

Full Load Current, I   =

3-phase Motor Power in KW *1000/( U * I *CosØ*√3*ɳ)

Here:

U = 415

CosØ = 0.8

ɳ = 0.88

Therefore, I =

(10 * 1000)/(415 * 0.8*0.88*√3) = 19.76 Amps


Important notes on Motor power calculations
The electrical power consumed by a single-phase motor in KW = U * I *CosØ/1000

Where the current here, I , is the full load or line current which MUST be given to calculate the power consumed by the motor. Unless otherwise clearly stated, the power rating of a motor in KW or Horsepower is always the shaft power in which case, the efficiency of the motor will be required to calculate the input power and thereafter the actual current the motor takes can then be calculated

Similarly, the electrical power consumed by a 3-phase motor in KW is given by:
U * I *CosØ*√3/1000

Where the current here, I , is the full load or line current which MUST be given to calculate the power consumed by the motor. Unless otherwise clearly stated, the power rating of a motor in KW or Horsepower is always the shaft power in which case, the efficiency of the motor will be required to calculate the input power and thereafter the actual current the motor takes can then be calculated

Contactor Operating Principle and Standards

Custom Search

What is a Contactor?
A contactor is an electrical device used for switching an electrical circuit on or off. It is similar to a relay, but the main difference is that the contactor is applied in high current carrying capacity applications and the relay used for low current applications.

Generally, these electrical devices feature multiple contacts. These contacts are in most cases normally open and provide operating power to the load when the contactor coil is energized. Contactors are mostly used for controlling electric motors.

There are various types of contactors, and each type has its own set of features, capabilities, and applications. Contactors can break current over a wide range of currents, ranging from a few amperes to thousands of amperes, and voltages from 24 VDC to thousands of volts. In addition, these electrical devices come in various sizes, from palm dimensions to sizes measuring a meter or yard on one side (approximately).

The most common application area of the contactor is high-current load. Contactors are known for their capability to handle currents of over 5,000 amperes and high power over 134Hp

Main Components of the Contactor
The electrical contactor has three (3) main components namely the (i) Coil (Electromagnet) (ii) Enclosure (iii) Contacts.

The Coil or Electromagnet provides the driving force that is required to close the contacts of the contactor. The coil and contacts are protected by an enclosure.

The enclosure provides insulation and protection from personnel touching the contacts. The protective enclosure is made from different materials, such as polycarbonate, polyester, Nylon 6, Bakelite, thermosetting plastics, and others. 

The contacts of the contactor are responsible for carrying rated current to the load the contactor powers. There are different types of contacts in a contactor namely, contact springs, auxiliary contacts, and power contacts. Each type of contact has an individual role to play.

Symbols of Contactors in Wiring Diagrams
Below are typical representations of contactors in electrical and control wiring diagrams:


Operating Principle of a Contactor
When current is supplied to a contactor, the electric current excites the electromagnet. The excited electromagnet produces a magnetic field, causing the contactor core to move the armature as shown in our schematic below:

 A normally closed (NC) contact completes the circuit between the fixed contacts and the moving contacts. This permits the current to pass through these contacts to the load. When current is removed, the coil is de-energized, and the circuit is open. The contacts of the contactors are known for their rapid open and close action.

One unique quality of contactors is that their coils can be powered by both DC and AC currents. Typical voltages include 12VDC, 24VDC and 220V AC with the most popular in use being the 24V DC for many control circuit applications. Contactors are primarily used for controlling single and three-phase motors and switching power circuits.

Contactor Standards
There are two standards for contactors: NEMA and IEC. 

NEMA Contactors
NEMA means National Electrical Manufacturers Association. NEMA contactors also are designed with safety factors that go beyond design ratings (oversized), up to as much as 25%. NEMA is primarily a North American Standard. NEMA contactors for low-voltage motors (less than 1,000 volts) are rated according to NEMA size, which gives a maximum continuous current rating and a rating by horsepower for attached induction motors. NEMA standard contactor sizes are designated 00, 0, 1, 2, 3 to 9. The table below details standard NEMA Contactors and Motor starters:

NEMA CONTACTOR AND MOTOR STARTER SIZES

NEMA Size

Max. Continuous Current (A)

Max. HP at 200V AC

Max. HP at 230V AC

Max. HP at 480/575V AC

00

9

1.5

1.5

2

0

18

3

3

5

1

27

7.5

7.5

10

2

45

10

15

25

3

90

25

35

50

4

135

40

50

100

5

270

75

100

200

6

540

150

200

400

7

810

-

300

600

8

1215

-

450

900

9

2250

-

800

1600


IEC Contactors
IEC means International Electrotechnical Commission and it is a global standard. IEC contactors are not oversized. They are smaller than NEMA contactors and less expensive. The range of sizes offered by manufacturers is more numerous than the ten NEMA standards. As such, they are more specific to a given application and are specified when the operating conditions are well understood. Whereas NEMA may be chosen when operating conditions, such as load are not well defined. The table below illustrates the IEC contactors utilization categories low voltage applications.

IEC UTILIZATION CATEGORIES

LOW VOLTAGE UTILIZATION CATEGORIES

Nature of Current

Category

Typical Applications

Relevant IEC product category

A.C

AC-1

Non-inductive or slightly inductive loads, resistance furnaces.

60947-4

AC-2

Slip-ring motors: starting, switching off.

AC-3

Squirrel-cage motors: starting, switching off motors during running.

AC-4

Squirrel-cage motors: starting, plugging1, inching2

AC-5a

Switching of electric discharge lamp control.

AC-5b

Switching of incandescent lamps.

AC-6a

Switching of transformers.

AC-6b

Switching of capacitor banks.

AC-7a

Slightly inductive loads in household appliances and similar applications.

AC-7b

Motor-loads for household applications.

AC-8a

Hermetic refrigerant compressor motor control with manual resetting of overload releases.

AC-8b

Hermetic refrigerant compressor motor control with automatic resetting of overload releases.

AC-12

Control of resistive loads and solid-state loads with isolation by optocoupler.

60947-5

AC-13

Control of solid-state loads with transformer isolation.

AC-14

Control of small electromagnetic loads.

AC-15

Control of A.C electromagnetic loads.

AC-20

Connecting and disconnecting under no-load conditions.

60947-3

AC-21

Switching of resistive loads, including moderate overloads.

AC-22

Switching of mixed resistive and inductive loads, including moderate overloads.

AC-23

Switching of motor loads or other highly inductive loads.

A.C and D.C

A

Protection of circuits, with no rated short-time withstand current.

60947-2

B

Protection of circuits, with a rated short-time withstand current.

D.C

DC-1

Non-inductive or slightly inductive loads, resistance furnaces.

60947-4

DC-3

Shunt-motors, starting, plugging1, inching2, dynamic breaking of motors.

DC-5

Series-motors, starting, plugging1, inching2, dynamic breaking of motors.

DC-6

Switching of incandescent lamps.

DC-12

Control of resistive loads and solid-state loads with isolation by optocouplers.

60947-5

DC-13

Control of D.C electromagnets.

DC-14

Control of D.C electromagnetic loads having economy resistors in circuit.

DC-20

Connecting and disconnecting under no-load conditions.

60947-3

DC-21

Switching of resistive loads, including moderate overloads.

DC-22

Switching of mixed resistive and inductive loads, including moderate overloads, (e.g. shunt motors).

DC-23

Switching of highly inductive loads, (e.g. series motors).

1By plugging is understood stopping or reversing the motor rapidly by reversing motor primary connections while the   motor is running.

 

2By inching (jogging) is understood energizing a motor once or repeatedly for short periods to obtain small movements of the driven mechanism.

 

Source: ©International Electrotechnical Commission


Difference between NEMA and IEC Contactors
Below is a comparison between NEMA and IEC contactors already discussed:

IEC

NEMA

Less Expensive

More Expensive

More Compact

Larger design

Global Market

North American Market

Less versatile: IEC contactors are specific application requirements

More versatile: A NEMA contactor can cover a broader range of applications

Finger Safe

Safety covers required

Faster reaction to overloads

Can handle short circuits better


Contactor Terms and Ratings
The table gives explanation of the common terms and ratings used with contactors designed based on the IEC global standard:
Circuits
Auxiliary circuit
All the conductive parts of a contactor designed to be inserted in a different circuit from the main circuit and the contactor control circuits.

Control circuit
All the conductive parts of a contactor (other than the main circuit and the auxiliary circuit) used to control the contactor's closing operation or opening operation or both.

Main circuit
All the conductive parts of a contactor designed to be inserted in the circuit that it controls.
Coil operating range Expressed as a multiple of the rated control circuit voltage Uc for the lower and upper limits
Cycle time
This is the sum of the current flow time and the no-current time for the given cycle.

Electrical durability
Number of on-load operating cycles that the contactor is able to carry out. It depends on the operational current, the operational voltage, and the utilization category.

Mechanical durability
Number of no-current operating cycles that a contactor can carry out.
Endurance/durability
Electrical endurance
The number of on-load operating cycles (i.e., with the current on the main contacts) a contactor can achieve, varies depending on the utilization category.

Mechanical endurance
The number of off-loading operating cycles (i.e., without current on the main contacts) a contactor can achieve.
Inching Energizing a motor once or repeatedly for short periods to obtain small movements of the driven mechanism.
Intermittent Duty Duty in which the main contacts of a contactor remain closed for periods of time insufficient to allow the contactor to reach thermal equilibrium, the current-carrying periods being separated by off-load periods of sufficient duration to restore equality of temperature with the cooling medium.
Rated breaking capacity.
Rated making capacity
Value of RMS current a contactor can break or make at a fixed voltage value, within the conditions specified by the standards, depending on the utilization category.
Rated control circuit
voltage Uc
Control voltage value for which the control circuit of the unit is sized.
Rated insulation voltage Ui Voltage value which designates the unit and to which dielectric tests, clearance, and creepage distances are referred.
Rated impulse withstand voltage, Uimp The highest peak value of an impulse voltage of prescribed form 1.2/50, which does not cause breakdown under specified test conditions.
Rated operating current Ie Current value stated by the manufacturer and considering the rated operating voltage Ue, the rated frequency, the rated duty, the utilization category, the electrical contact life and the type of protective enclosure.
Rated operating voltage Ue Voltage value to which utilization characteristics of the contactor are referred, i.e., phase to phase voltage in 3 phase circuits.
Conventional thermal
current Ith
Value of current the contactor can withstand with poles in closed position, in free air for an eight-hour duty, without the temperature rise of its various parts exceeding the limits specified by the standards.
Making and breaking
current
Current at contactor closing or at contactor opening.
Resistance to shocks Requirements applicable for instance to vehicles, crane operation or switchgear slide-in module systems. At the quoted permissible «g» values, contactors must not undergo a change in switching state and overload relays must not trip.
Resistance to vibration Requirements applicable to all the vehicles, vessels and other similar transport systems. At the quoted amplitude and vibration frequency values, the unit must be capable to achieve the required duty.
Times
Closing time
Time between energization of the coil until the moment the contacts of the first current path to be closed, actually close.

Opening time
Time between de-energization of the coil until the moment when the contacts of the last current path to be opened are open.

Minimal operation time
Shortest control duration to ensure complete closing or opening of a contactor.

Short time current permissible
Value of current which the contactor can withstand in closed position for a short time period and within specified conditions.

Time constant
Ratio of inductance to the resistance: L/R = mH/Ohm = ms.

Cycle duration
Total time of the on-load + off-load period.

You May Also Like: